Specifications |
|
System |
|
Unit Type |
|
MXZ-5D42NL |
Cooling at 95F^{1} (Non-Ducted // Mixed // Ducted) |
Maximum Capacity |
Btu/h |
43,000 // 41,000 // 39,000 |
|
Rated Capacity |
Btu/h |
40,500 // 38,000 // 36,400 |
|
Minimum Capacity |
Btu/h |
12,600 // 12,600 // 12,600 |
|
Maximum Power Input |
W |
4,400 // 4,495 // 4,590 |
|
Rated Power Input |
W |
4,355 // 4,200 // 4,044 |
|
Power Factor (208V) |
% |
0.99 // 0.99 // 0.99 |
|
Power Factor (230V) |
% |
0.99 // 0.99 // 0.99 |
Heating at 47F^{2} (Non-Ducted // Mixed // Ducted) |
Maximum Capacity |
Btu/h |
53,600 // 47,300 // 41,000 |
|
Rated Capacity |
Btu/h |
45,000 // 43,000 // 41,000 |
|
Minimum Capacity |
Btu/h |
12,800 // 12,800 // 12,800 |
|
Maximum Power Input |
W |
5,500 // 5,885 // 6,270 |
|
Rated Power Input |
W |
4,397 // 4,457 // 4,518 |
|
Power Factor (208V) |
% |
0.99 // 0.99 // 0.99 |
|
Power Factor (230V) |
% |
0.99 // 0.99 // 0.99 |
Heating at 17F^{3} (Non-Ducted // Mixed // Ducted) |
Maximum Capacity |
Btu/h |
30,500 // 29,800 // 29,100 |
|
Rated Capacity |
Btu/h |
29,000 // 27,600 // 26,200 |
|
Maximum Power Input |
W |
4,450 // 4,840.50 // 5,231 |
|
Rated Power Input |
W |
3,295 // 3,427 // 3,589 |
Heating at 5F^{4} (Non-Ducted // Mixed // Ducted) |
Maximum Capacity |
Btu/h |
25,000 // 22,400 // 20,000 |
|
Maximum Power Input |
W |
4,164 // 4,208 // 4,247 |
Efficiency (Non-Ducted // Mixed // Ducted) |
SEER2^{1} |
|
19.30 // 17.45 // 15.60 |
|
EER2^{1} |
|
9.30 // 9.15 // 9 |
|
HSPF2 (IV)^{2} |
|
9.10 // 8.55 // 8 |
|
COP at 47°F^{2} |
|
3 // 2.82 // 2.66 |
|
COP at 17°F at Maximum Capacity^{3} |
|
2 // 1.80 // 1.62 |
|
COP at 5°F at Maximum Capacity^{4} |
|
1.76 // 1.56 // 1.38 |
|
ENERGY STAR^{®} Certified |
|
No // No // No |
Electrical |
Electrical Power Requirements |
V AC / V AC, ø, Hz |
208 / 230, 1, 60 |
|
Guaranteed Voltage Range |
V AC |
198 - 253 |
|
Voltage: Indoor - Outdoor, S1-S2 |
V AC |
208/230 |
|
Voltage: Indoor - Outdoor, S2-S3 |
V DC |
24 |
|
Recommended Wire Size (Indoor - Outdoor) |
AWG |
14 |
|
Short-circuit Current Rating (SCCR) |
kA |
5 |
|
MCA |
A |
39.2 |
|
MOCP |
A |
67 |
|
NOTES
^{1} Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB)
^{2} Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB)
^{3} Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB)
^{4} Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB)
Capacity varies based on the number of indoor units operating and the model of the Multi-zone Outdoor Unit. For reference to connected capacity charts, please refer to Multi-zone Outdoor Unit Oper-ational Performance.
For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance.
Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity.
Please utilize this over capacity capability for load shedding or applications where it is known that all connected units will NOT be operating at the same time.
^{*} Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode and automatically restarts at these temperatures. |
Specifications are subject to change without notice. |
|
|
|